TYPE |
220V Series |
380V Series |
500V Series |
690V Series |
|
Nominal voltage |
AC220V±20% |
AC380V±20% |
AC500V±20% |
AC690V±20% |
|
Rated frequency |
50Hz±5% |
50Hz±5% |
50Hz±5% |
50Hz±5% |
|
compensating current |
25A |
25A、50A、75A、100A、150A |
100A |
100A |
|
Network |
L/N |
Three-phase three-wire/ three-phase four-wire |
|||
Numbers in parallel |
No limitation |
||||
Machine efficiency |
≥97% |
≥97% |
≥97% |
≥97% |
|
Switching frequency |
32kHz |
16kHz |
12.8kHz |
12.8kHz |
|
Feature selection |
Deal with reactive power/ deal with harmonics and reactive power |
||||
Reactive power compensation rate |
>95% |
>95% |
>95% |
>95% |
|
Harmonic Compensation range |
2nt to 50th harmonic, single compensation rated is adjustable |
||||
Harmonic compensation rate |
>92% |
>92% |
>92% |
>92% |
|
Response time |
<10ms |
<40ms |
<40ms |
<40ms |
|
Noise |
≤60dB |
≤60dB |
≤65dB |
≤65dB |
|
Communication method |
Two channel RS485 communication interface ( support GPRS/WIFI wireless communication) |
||||
Protection function |
Over load protection, hardware/software over current protection, over grid power protection /under grid power protection, power failure protection, over temperature protection, frequency anomaly protection, short circuit protection, etc |
Over load protection, hardware/software over current protection, over grid power protection /under grid power protection, grid power voltage imbalance protection, power failure protection, over temperature protection, frequency anomaly protection, short circuit protection, etc |
|||
Installation |
Rack/ wall mounted |
Rack/ wall mounted |
Rack |
Rack |
|
Connection |
Back entry ( rack type) |
Back entry ( rack type) |
Back entry |
Back entry |
|
Top entry (wall mounted) |
Top entry (wall mounted) |
||||
Protection grade |
IP20 |
IP20 |
IP20 |
IP20 |
|
Altitude |
<2000m,above 2000m decrease rate according to GB/T3859.2 |
||||
Temperature |
-20~+50℃ |
-20~+50℃ |
-20~+50℃ |
-20~+50℃ |
|
Humidity |
≤90%,the average monthly minimum temperature is 25℃ without condensation on the surface |
||||
Pollution level |
Below level Ⅲ |