Home Categories Send inquiry

Active Harmonic Filters(AHF-150-0.4-4L-W)

Product Summary

Active Harmonic Filters (AHF) An active harmonic filter is a type of electronic device that is used to mitigate or eliminate harmonic distortions in electrical power systems. Harmonic distortion refers to the presence of unwanted frequencies in the power system that can lead to issues such as increased heating of equipment, reduced system efficiency, and even equipment failure.
AHF operates by sensing the harmonic currents in the system and generating a counter-current of the same magnitude and opposite phase. This counter-current cancels out the harmonic current and prevents it from being fed back into the power system. Active harmonic filters are designed to be fast and accurate in their response to changing harmonic conditions in the power system.
Active harmonic filters are commonly used in industrial and commercial settings where there are high levels of non-linear loads, such as variable frequency drives, uninterruptible power supplies, and computer equipment. They are also used in power quality improvement applications in residential and commercial buildings.

Working Principle

External CT detects the load current, DSP as CPU has advanced logic control arithmetic, could quickly track the instruction current, divides the load current into active power and reactive power by using the intelligent FFT, and calculates the harmonic content rapidly and accurately. Then it sends PWM signal to internal IGBT's driver board to control IGBT on and off at 20KHZ frequency. Finally generates opposite phase compensation current on inverter induction, at the same time CT also detects the output current and negative feedback goes to DSP. Then DSP proceeds the next logical control to achieve more accurate and stable system.

Technical Specifications

TYPE 220V  Series 400V  Series 500V Series 690V Series
Rated compensation current 23A 15A、25A、50A
75A、100A、150A
100A 100A
Nominal voltage AC220V
(-20%~+15%)
AC400V
(-40%~+15%)
AC500V
(-20%~+15%)
AC690V
(-20%~+15%)
Rated frequency 50/60Hz±5%
Network Single phase 3 phase 3 wire/3 phase 4 wire
Response time <40ms
Harmonics filtering 2nd to 50th Harmonics,The number of compensation can be selected,and the range of single compensation can be adjusted
Harmonic compensation rate >92%
Neutral line filtering capability / The filtering capacity of 3 phase 4 wire neutral line is 3 times of that of phase fiitering
Machine efficiency >97%
Switching frequency 32kHz 16kHz 12.8kHz 12.8kHz
Function Deal with harmonics
Numbers in parallel No limitation.A single centralized monitoring module can be equipped with up to 8 power modules
Communication methods Two-channel RS485 communication interface (support GPRS/WIFI wireless communication)
Alfitude without derating <2000m
Temperature -20~+50℃
Humidity <90%RH,The average monthly minimum temperature is 25°C without condensation on the surface
Pollution level Below level III
Protection function Overload protection,hardware over-current protection,over-voltage protection,power failure protection,over-temperature protection,frequency anomaly protection,short circuit protection,etc
Noise <50dB <60dB <65dB
nstallation Rack/Wall-mounted
Into the way of line Back entry(rack type),top entry(wall-mounted type)
Protection grade IP20

 

 